Washington DC Data Centre

Commitment to Compliance

CenturyLink is dedicated to continuously improving and maintaining compliance and standards that are critical to customers.

Washington DC Area Data Centres: Supporting Global Connections

Washington DC is home to Fortune 500 companies and some of the most important financial institutions in the world. It also hosts the largest IP peering connection point in North America.

Six of the 60+ CenturyLink data centres are located in metro Washington DC. Combined, the Washington DC data centres supply 329,000 sq/ft of premium co-location space that empowers this vital communications nucleus. Designed to meet strict networking and IT security demands of enterprise, government and financial institutions, the Washington DC data centres offer failsafe critical systems infrastructure, powerful cross connects, and multi-tier security measures that can be augmented for specific security requirements. From these facilities, technology connects markets across the globe.

Announcements

Take a Virtual Tour of our CH3 Data Centre

Data Centres

Washington DC Data Centre Locations

Locations

DC2: Sterling, VA

Space: 88,489 sf   Power: 6 MW

Tech Specs

DC2: Sterling, VA     Space: 88,489 sf     Power: 6 MW

Real Estate Summary

  • Located near Dulles International and Reagan National Airports; 40 minutes from Washington, D.C.
  • One story building
  • Total building interior (sf) = 88,489
  • Raised floor (inches) = 12

Electrical Summary

  • Dominion Virginia Power provides power feeds
  • Power density minimum (W/sf) = 150
  • Generator configuration = N + 1
  • Total Power Capacity = 6 MW
  • Minimum two fuel replenishing companies

Fire Detection and Suppression Summary

  • VESDA provides early warning detection
  • Pre-Action system utilises two detection methods; one ionized and one photo electric detector interlocked with the dry pipe sprinkler system

Mechanical Summary

  • Cooling system configuration = N +1
  • CenturyLink manages temperature and humidity to strict ASHRAE standard

DC3: Sterling, VA

Space: 78,671 sf   Power: 8 MW

Tech Specs

DC3: Sterling     Space: 78,671 sf     Power: 8 MW

Real Estate Summary

  • Located near Dulles International and Reagan National Airports; 40 minutes from Washington, D.C.
  • One story building
  • Total building interior(sf) = 78,671
  • Raised floor (inches) = 24

Electrical Summary

  • Dominion Virginia Power provides power feeds
  • Power density minimum (W/sf) = 150
  • Generator configuration = N + 1 + 1
  • Total Power Capacity = 8 MW
  • Minimum two fuel replenishing companies

Fire Detection and Suppression Summary

  • VESDA provides early warning detection
  • Pre-Action system utilises two detection methods; one ionized and one photo electric detector interlocked with the dry pipe sprinkler system

Mechanical Summary

  • Cooling system configuration = N + 1
  • CenturyLink manages temperature and humidity to strict ASHRAE standard

DC4: Sterling, VA

Space: 135,513 sf   Power: 12 MW

Tech Specs

DC4: Sterling     Space: 135,513 sf     Power: 12 MW

Real Estate Summary

  • Located near Dulles International and Reagan National Airports; 40 minutes from Washington, D.C.
  • One story building
  • Total building interior (sf) = 135,513
  • Raised floor (inches) = 30

Electrical Summary

  • Dominion Virginia Power provides power feeds
  • Power density minimum (W/sf) = 150
  • Generator configuration = N + 1 + 1
  • Total Power Capacity = 12 MW
  • Minimum two fuel replenishing companies

Fire Detection and Suppression Summary

  • VESDA provides early warning detection
  • Pre-Action system utilises two detection methods; one ionized and one photo electric detector interlocked with the dry pipe sprinkler system

Mechanical Summary

  • Cooling system configuration = N + 1
  • CenturyLink manages temperature and humidity to strict ASHRAE standard

DC5: Sterling, VA

Space: 47,508 sf   Power: 3.2 MW

Tech Specs

DC5: Sterling     Space: 47,508 sf     Power: 3.2 MW

Real Estate Summary

  • Located near Dulles International and Reagan National Airports; 40 minutes from Washington, D.C.
  • One story building
  • Total building interior (sf) = 47,508
  • Raised floor (inches) = 24

Electrical Summary

  • Dominion Virginia Power provides power feeds
  • Power density minimum (W/sf) = 150
  • Generator configuration = N + 1
  • Total Power Capacity = 3.2 MW
  • Minimum two fuel replenishing companies

Fire Detection and Suppression Summary

  • VESDA provides early warning detection
  • Pre-Action system utilises two detection methods; one ionized and one photo electric detector interlocked with the dry pipe sprinkler system

Mechanical Summary

  • Cooling system configuration = N + 1
  • CenturyLink manages temperature and humidity to strict ASHRAE standard

DC6: Sterling, VA

Space: 71,033 sf   Power: 13.6 MW

Tech Specs

DC6: Sterling     Space: 71,033 sf     Power: 13.6 MW

Real Estate Summary

  • Located near Dulles International and Reagan National Airports; 40 minutes from Washington, D.C.
  • One story building
  • Total building interior (sf) = 71,033
  • Raised floor (inches) = 24

Electrical Summary

  • Dominion Virginia Power provides power feeds
  • Power density minimum (W/sf) = 150
  • Generator configuration = N + 1
  • Total Power Capacity = 13.6 MW
  • Minimum two fuel replenishing companies

Fire Detection and Suppression Summary

  • VESDA provides early warning detection
  • Pre-Action system utilises two detection methods; one ionized and one photo electric detector interlocked with the dry pipe sprinkler system

Mechanical Summary

  • Cooling system configuration = N + 1
  • CenturyLink manages temperature and humidity to strict ASHRAE standard

DC7: Sterling, VA

Space: 135,243 sf   Power: 4.8 MW

Tech Specs

DC7: Sterling     Space: 135,243 sf     Power: 13.6 MW

Real Estate Summary

  • Located near Dulles International and Reagan National Airports; 40 minutes from Washington, D.C.
  • One story building
  • Total building interior (sf) = 135,243
  • Raised floor (inches) = 36

Electrical Summary

  • Dominion Virginia Power provides power feeds
  • Power density minimum (W/sf) = 150
  • Generator configuration = N + 1
  • Total Power Capacity = 4.8 MW
  • Minimum two fuel replenishing companies

Fire Detection and Suppression Summary

  • VESDA provides early warning detection
  • Pre-Action system utilises two detection methods; one ionized and one photo electric detector interlocked with the dry pipe sprinkler system

Mechanical Summary

  • Cooling system configuration = N + 1
  • CenturyLink manages temperature and humidity to strict ASHRAE standard

More Locations

Over 60 Data Centre Locations Worldwide

Latest from the EpiCenter Blog

Discussing the Data Centre of the Future

Michael Levy | March 13,2017

Many children grow up with toys you'd expect: bicycles, stuffed animals, dolls, building blocks, etc. It wouldn't be surprising to find a Magic-8 Ball in their arsenal that gives them ambiguous answers to the many seemingly important questions in childhood. … Read more…→ The post Discussing the Data Centre of the Future appeared first on CenturyLink EpiCenter Blog.

Operational Excellence: By the Book

David Meredith | March 07,2017

This article was previously published in Forbes Voice. Many large technology products come with a handbook when purchased. For example, if you buy a new large-screen television, the box in which it comes typically includes a handbook on how to … Read more…→ The post Operational Excellence: By the Book appeared first on CenturyLink EpiCenter Blog.

Operational Excellence: The Key to Safeguarding Your IT Infrastructure

Kelly Sullivan | March 01,2017

Technology can streamline mundane tasks, enable people to more easily keep in contact with family and friends around the world and allow TV shows and movies to be viewed almost anytime and anywhere. However, when it doesn't work correctly, it … Read more…→ The post Operational Excellence: The Key to Safeguarding Your IT Infrastructure appeared first on CenturyLink EpiCenter Blog.

CenturyLink
Business
@CenturyLink ENT

Resources

Get Started with Featured Resources and Tools

Get Started
Request Consultation

Request Consultation

Call Us

Call Us

SALES: +65 6768 8098 
SUPPORT: +65 6768 8099

Get Connected. See What's Next for Business.